Technical Specification for Stationary VRLA Cells (DIN 40742) |
 |
Application |
The Power Safe OPzV range are valve regulated lead-acid cells which use a proven combination of GEL and tubular technologies to offer a very high level of reliability.
These single cells benet from an optimized plate design which gives capacities in excess of the DIN standard values.
In addition, the Power Safe OPzV range offers both a long float life and a high cycle life for a truly flexible solution.
Click here to view the technical brochure
Power Safe OPzV batteries are suitable for a broad range of applications including telecommunications, telephony, power generating stations and distribution systems, railway, airport and seaport signalling, computing, emergency lighting, automation and measuring systems.
 |
Features & Benefits |
• Capacity range: 215Ah to 3170Ah
• C10 capacities exceed the DIN standard values
• Highest EUROBAT classification ‘Long Life’
• Excellent deep discharge recovery and cyclability
• Increased operational safety with fully insulated connectors, immobilized electrolyte and one way pressure relief valve with an integral flame arrestor
• Easy installation: vertical or horizontal position
• Very low maintenance: no water addition
 |
Construction |
Positive Electrode - Tubular plate with Lead-Calcium-Tin alloy
Negative Electrode - Flat plate with Lead- Calcium alloy grid
Separator - Low resistance microporous material
Case Material - Container and lid in ABS; optional flame retardant ABS available (UL94 V-0)
Electrolyte - Sulfuric acid, immobilized as a gel
Terminal Design - Terminals with brass insert and M10 stainless steel bolts.
Coloured washers are provided for easy polarity recognition
Connectors - Insulated solid copper connector (0.79” x 0.12”) for vertical installations or insulated flexible cable connectors for horizontal installations.
Each connector design is of the bolt-on type and allows for voltage measurements
Pressure Relief Valve - One way valve with integral flame arrestor
 |
Operation |
• Recommended float charge voltage:
- 2.25Vpc at 20°C (68°F) and 2.23Vpc at 25°C (77°F)
• Recommended temperature range:
-10°C to 45°C (14°F to 113°F) preferred value 20°C (68°F)
• Cells can be installed horizontally to minimize use of floor space
• Optional racking offers easy installation and space saving accommodation
 |
Standards |
• Conforms to both the DIN standard 40742 (valve regulated OPzV single cells) and the international standard IEC 60896-2
• Classified as ‘long life’ according to the EUROBAT guide 1999
• Low ventilation requirement according to EN 50272-2
• EnerSys manufacturing facilities worldwide are certified to ISO 9001
 |
Fields |
• Telecommunications
• Emergency lighting
• Microwave radio systems
• Power generation plants
• Photovoltaics
|