Application
IIB OPzV - Batteries belongs to the best EUROBAT classification for maintenance free lead - acid - batteries: 10+ high integrity. In applications with high requirements of operational safety and bridging times of 1h to more than 10h the IIB OPzV is the right choice.

They are used as standby power sources in telecommunications microwave - radio stations, emergency light equipment and other equipment¹s
 
Types, capacities, dimensions, mass
Type
C10
C5
C3
C1
Ri
Ik
length
width
height
(max.)
mass
lead
mass
 .
Ah
Ah
Ah
Ah
mW
kA
mm
mm
mm
kg
kg
Ue   V/cell 
1,80
11,78
1,75
1,67
.  .  .  .  .  .  . 
12V 1 OPzV 50
59
47
44
34
21,60
0,58
272
205
385
42,5
28
12V 2 OPzV 100
107
97
88
69
10,80
1,15
272
205
385
50,5
38
12V 3 OPzV 150
169
143
127
101
7,20
1,73
380
205
385
72
53
6V 4 OPzV 200
219
192
173
129
2,70
2,30
272
205
385
48
35
6V 5 OPzV 250
276
242
212
165
2,16
2,88
380
205
385
63
43
6V 6 OPzV 300
326
291
255
200
1,80
3,45
380
205
385
70
50
2V 12 OPzV 600
654
572
514
383
0,30
6,90
205
272
385
48
35
2V 15 OPzV 750
828
721
630
489
0,24
8,63
205
380
385
63
43
2V 18 OPzV 900
973
867
758
593
0,20
10,35
205
380
385
70
50
12V 1 OPzV 50 to
12V 3 OPzV 150
6V 4 OPzV 200 to
6V 6 OPzV 300
2V 12 OPzV 600 to
2V 18 OPzV 900
 
Design
positive electrode  tubular plate with a woven polyester gauntlet and solid grids in a corrosion- resistant PbCaSn - alloy
negative electrode  grid plate in PbCaSn - alloy with long - life expander
separation microporous separator
elektrolyte sulphuric acid with a density of 1,24 kg/l, fixed as GEL by fumed silica
container high-impact, halogene-free SAN, grey coloured; UL-rating 94HB
lid  high-impact, halogene-free SAN, grey coloured, UL-rating 94HB
blocks with blind cells  4V, 6V, 8V, 10V
valve  one valve per cell with flame arrestor
opening pressure approx. 100 mbar,
closing pressure approx. 50 mbar
pole - bushing  100% gas- and electrolyte-tight, sliding-pole
kind of pole  M10 brass insertion
connectors  flexible insulated copper cables, with cross-section of
35, 50, 70, 95 mm²
kind of protection  IP 25 regarding DIN 40050, touch - protected according to VBG 4.
 
Charging
IU - characteristic  Imax without limitation
U = 2,23 to 2,25 V/cell +- 1%, between 10°C and 45°C
D U/D T = -0,004 V/K below 10°C in the monthly average
boost charge  U = 2,35 to 2,40V/cell, time limited
charging time up to 90%  6h with 1,5*I10 initial current, 2.23 V/cell, 50% C10 discharged
 
Discharge characteristics
reference temperature 20°C
initial capacity 100%
Entladetiefe depth of discharge (DOD) normally up to 80%
Tiefentladungen deep discharges more than 80% DOD or discharges beyond final discharge
voltages (dependent on discharge current) have to be avoided
Erholung nach Tiefentladung deep discharge recovery the GEL design allows a complete recharging after an unwanted deep discharge
 
Maintenance
every 6 months  check battery voltage, pilot block voltage, temperature
every 12 months  record battery and block voltages and temperatures
 
Operational data
classification according
to EUROBAT 
10+, high integrity
operational life  > 12 to 15 years at 20°C
> 6 to 7,5 years at 30°C
> 3 to 4 years at 40°C
maintenance-free  no topping-up during life
IEC 896-2 cykles 1200
self-discharge  app. 2% per month at 20°C
operational temperature  -20°C to 45°C
recommended 10°C to 30°C
deep discharge recovery  very good
ventilation requirement  25% (f1=0,5 x f2=0,5) according to VDE 0510 part 2
applicable standards  IEC 896-2, VDE 0510, part 2
standard DIN 40 744
transport no dangerous goods during air-, sea- and land transport
Israel Industry Batteries Goren Indudtrial Zone, P.O.B. 1022 - Post Mobile, Western Galilee, 22850, Tel: +972-4-9807766, Fax: +972-4-9807755